XCELL BOILER ROOM CASE STUDIES

 

Case Study # 2

Project Installation: State Farm, Corp. South; Bloomington, Illinois

System Design: XCELL Mechanical Systems
System Installation: XCELL Mechanical Systems

The Client
The State Farm, Corporate South facility is a 3,000,000 sq. ft. complex which serves as the data processing headquarters for one of the largest insurance companies in the world.
The Problem
  • Wide, seasonal load swings, which created tremendous boiler stresses
  • Recurring Kewanee Phoenix burner head damage and subsequent repair
The State Farm, Corporate South facilities hot water heating system requirements are fulfilled by two Kewanee, firetube boilers, which had experienced recurring burner head failures. This building has tremendously large seasonal load variations which range from 700 H.P. in the cold of the winter, to as low as 69 H.P. in the heat of the summer.
This extremely wide operating range caused a variety of burner and boiler problems which included burner head failures as a result of operating the burners at extremely low firing rates which caused burner head over-heating. Boiler stress as a result of on-off cycling was causing recurring tube and knuckle waterside vessel failures.
Summary : Extremely wide seasonal load swings, boiler waterside vessel failure and burner head overheat failure.
 

XCELL BOILER ROOM SOLUTION

 

XCELL's  Exclusive Portable Burner System

  • The most cost effective solution to the extremely wide seasonal load swings, which are experienced at State Farm, Corporate South and most similar facilities, is to provide burner firing rates which will more accurately match up with system loads.

  • Since building loads regularly approach a 15 to 1 turndown ratio and even the higher turndown burners like the Industrial Combustion D-Series, are limited to a 10 to 1 turndown in firing rate, the answer is to use the portable burner concept, which is exclusive to XCELL Mechanical Systems. Seasonal burner changeouts take about 4 hours and can be performed by in-house personnel.

More Case Studies


Contact us for more information on how our engineers can find a solution to fit

your heating or boiler room needs.

Home ] Up ] Case Study #1 ] [ Case Study #2 ] Case Study #3 ] Case Study #4 ] Case Study #5 ] Case Study #6 ] Case Study #7 ]

Contact us for more information.

 

Copyright © 2006 Xcell Mechanical Systems

Xcell Mechanical Systems     30068 Route 9    Mackinaw, IL    (309) 359-3084

Commercial heating and air conditioning specialist serving central Illinois